entry |
PotisBank-A5.0-1500 |
PotisBank-A5.2-1500 |
|
|
Number of battery packs |
150.05kWh/m² |
156.05kWh/m² |
|
|
Battery cluster configuration |
1P400S( |
1P416S( |
|
|
Nominal voltage |
1280V |
1331.2V |
|
|
Voltage range |
Auxiliary power supply |
1081.6~1518.4V |
|
|
Rated energy |
5.0176 MWh |
5.218304MWh |
|
|
weight |
58Tons |
60Tons |
|
|
Cell type |
LFP |
|
|
|
Battery pack configuration |
1P16S |
|
|
|
Number of battery clusters |
14 |
|
|
|
Charge and discharge ratio |
0.5P |
|
|
|
Short-circuit current |
98kA |
|
|
|
Communication mode |
Ethernet/RS485/CAN |
|
|
|
Communication protocol |
Modbus TCP / Modbus RTU / CAN 2.0 |
|
|
|
Design standard |
GB/T 36276-2018, UN38.3, IEC62619,NFPA69, NFPA70, NFPA855,NFPA68 |
|
|
|
Auxiliary equipment power supply |
380V/480V |
|
|
|
Auxiliary power |
40kW |
|
|
|
Standby power supply |
2hour |
|
|
|
Operating ambient temperature |
-20℃ to 55℃(-4°to 131°F) |
|
|
|
Working altitude |
<2000m ( 2000m~4000m, Downpower operation) |
|
|
|
Thermal management |
air conditioner |
|
|
|
Size (length * width * height) |
13716*2438*2896mm |
|
|
|
Protection class |
IP20 |
|
|
|
color |
RAL9010 |
|
|
|
Seismic load strength |
Zone 4 |
|
|
|
Noise level |
70 dB(A) |
|
|
|
Fire protection system |
Heptafluoropropane or perfluorohexanone |
|
|
|
Spot stop |
Yes |
|
|
|
Remote emergency stop |
Yes |
|
|
|
Fire detection |
container |
|
|
|
Thermal diffusion technique |
Yes |
|
|
|
FCL delivery (built-in battery) |
Yes |
|
|
|
Battery protection class |
IP54 |
|
|
|
Full power operating range |
SOC5%~100%@25℃ |
|
|
|
Maximum number of cycles |
4 Times per day |
|
|